Model
110 / 2000 HE WOR
110-120 / 20A HE
Part number
241115.805
241119.805
INPUT DATA
Voltage range (nominal)
185 - 275 VAC/DC
176 - 277 VAC 1)
Voltage range
85 - 300 VAC/DC
85 - 305 VAC1)
Frequency
0 - 66 Hz
45 - 66 Hz
Maximum current
11.9 ARMS
18.64 ARMS
Power Factor
0.99 (@ 50-100 % load)
0.99 (@ 50-100 % load)
THD (@ 230 VAC)
< 5 % (@ full load)
< 4 % (@ full load)
Protection
Varistor for transient protection, fuse in both lines, shutdown above 300/305 V
OUTPUT DATA
Default voltage
122.5 VDC
Voltage range
89.22) - 171.6 VDC
90.02) - 151.25 VDC1)
# Pb cell supported (1.8 - 2.4 VDC/cell)
54 - 71
54 -60
# NiCad cell supported (1.05 - 1.65 VDC/cell)
85 - 104
86 - 91
Max power, nominal input
2000 W
3025 W1)
Max power, 85V input
850 W
1280 W
Max current
16.7 A
20 A
Hold-up time, default voltage and 1500 W load
20 ms, VOUT > 99.7 VDC
10 ms, VOUT > 99.7 VDC
Current sharing
±5% of maximum current from 10 to 100% load
Static voltage regulation
±0.5% from 10% to 100% load and nominal input
Dynamic voltage regulation
±5.0% for 10-80% or 80-10% load variation, regulation time < 50ms
Rippel and noise, 30 MHz bandwidth
< 500 mVPP
Protection
Overvoltage shutdown, short circuit proof, high temperature, hot plug-in inrush current
limiting, ORing diode
OTHER SPECIFICATIONS
Efficiency
> 94%
> 94%
Isolation
3.0 kVAC – input and output, 1.5 kVAC – input earth, 1.5 kVDC – output earth
3 kVAC CAN – input, 3kVAC CAN – output
Alarms (Red LED)
Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage
shutdown on output, Fan failure, Low voltage alarm, CAN bus failure
Warnings (Yellow LED)
Rectifier in power derate mode, Remote battery current limit activated, Input voltage out of
range, flashing at overvoltage
Normal (Green LED)
Input and output ok
MTBF (Telcordia SR-332 Issue I method III (a))
>391 000h (@TAMBIENT= 25°C)
>400 000h (@TAMBIENT= 25°C)
Operating temperature (5 - 95% RH non-cond.)
Output power de-rates above temp / to
-40 to +75°C [-40 to +167°F]
+55°C / 1350W @ +75°C
-40 to +75°C [-40 to +167°F]
+50°C / 1150 W @ +75°C
Storage temperature
-40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing
Dimensions[WxHxD] / Weight
109 x 41.5 x 327mm (WxHxD) [4.25 x 1.69 x 13”] / 1.950 kg [4.3lbs]
DESIGN STANDARDS
Electrical safety
UL 60950-1, EN 60950-1, CSA 22.2
EMC
ETSI EN 300 386 V.1.3.2
EN 61000-6-1 / -2 / -3 / -4 / -5
Mains Harmonics
EN 61000-3-2
Environment
ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2)
ETSI EN 300 132-2
2011/65/EU (RoHS) & 2008/98/EC (WEEE)
Marine compliance
(EMC class B with AC filter)
DnV Rules for Classification of Ships, High
Speed & Light Craft and DnV Offshore
Standards
Contact Us

Email: admin@kl-telecom

Mob.: +86 137 3025 6445

Add.: Jingdong Industrial park 1102 ,Fuxing Road,BaodingCity Hebei Province,China